Preview

ENERGETIKA. Proceedings of CIS higher education institutions and power engineering associations

Advanced search

Mathematical Simulation of Transient Parameters of Vertical Grounding Electrodes

Abstract

The paper contains a mathematical simulation of transient parameters of vertical grounding electrodes for the first and subsequent short strokes of a lightning current. Results of the research show that transient resistances of grounding electrodes change appreciably in time. The transient resistances are always higher in the moment of voltage maximum then in the moment of current maximum. The dependences of transient resistances on grounding electrode length at different ground conductivity and lightning current parameters (first and subsequent short strokes) are obtained in the paper. The paper proposes an approximate criterion for estimation of grounding electrode equivalent length at transient condition that considers short stroke parameters of the lightning current and ground conductivity.

About the Authors

D. A. Gerasimovich
Belarusian National Technical University
Belarus


A. A. Dziaruhina
Belarusian National Technical University
Belarus


References

1. Герасимович, Д. А. Метод расчета электромагнитных характеристик вертикальных стержневых заземлителей при стекании импульсных токов молнии / Д. А. Герасимович, Е. А. Дерюгина // Энергетика... (Изв. высш. учеб. заведений и энерг. объединений СНГ). – 2011. – № 6. – С. 12–20.

2. Кадомская, К. П. Моделирование волны тока молнии при расчетах грозоупорности электрических сетей / К. П. Кадомская, А. А. Рейхердт // Электричество. – 2006. – № 11. – С. 17–23.

3. Protection against lightning. Part 1: General principles: IEC 62305–1. – Ed. 1. – 2006. – 128 p.

4. Инструкция по устройству молниезащиты зданий, сооружений и промышленных коммуникаций: утв. М-вом энергетики Рос. Федерации 30.06.03. – М.: Изд-во МЭИ, 2004. – 57 с.

5. Heidler, F. Calculation of lightning current parameters / F. Heidler, J. M. Cvetić, B. V. Stanić // IEEE Trans. Power Del. – 1999. – Vol. 14, № 2. – P. 399–404.

6. Poljak, D. Wire antenna model for transient analysis of simple grounding systems, part I: the vertical grounding electrode / D. Poljak, V. Doric // Progress in Electromagnetics Re-search. – 2006. – Vol. PIER 64. – P. 149–166.

7. Герасимович, Д. А. Математическое моделирование электромагнитных характеристик уединенных бесконечно длинных стержневых заземлителей при стекании переменного тока промышленной частоты / Д. А. Герасимович, Е. А. Дерюгина // Энергетика... (Изв. высш. учеб. заведений и энерг. объединений СНГ). – 2010. – № 4. – С. 5–13.

8. Руководство по защите электрических сетей 6–1150 кВ от грозовых и внутренних перенапряжений: РД 153–34.3–35.125–99. – Введ. 12.07.1999. – СПб.: Изд-во ПЭИПК, 1999. – 227 с.

9. Базелян, Э. М. Особенности работы заземлителей молниеотводов в грунтах низкой проводимости / Э. М. Базелян, М. И. Чичинский // Электрические станции. – 2005. – № 8. – С. 75–82.

10. Экспериментальные исследования заземлителей молниезащиты при воздействии импульсных токов / Р. К. Борисов [и др.] // Электро. – 2004. – № 1. – С. 13–16.


Review

For citations:


Gerasimovich D.A., Dziaruhina A.A. Mathematical Simulation of Transient Parameters of Vertical Grounding Electrodes. ENERGETIKA. Proceedings of CIS higher education institutions and power engineering associations. 2012;(1):9–16. (In Russ.)

Views: 827


Creative Commons License
This work is licensed under a Creative Commons Attribution 4.0 License.


ISSN 1029-7448 (Print)
ISSN 2414-0341 (Online)