Abstract

This article discusses the factors that affect the electrical resistance of the current spreading of the grounding device. The issue of the electrophysical parameters of the soil that affect its resistivity and the consideration of such parameters in the design of grounding devices is considered. It is shown that keeping moisture in the near-electrode space of the grounding electrode, as well as maintaining it at a certain level, facilitates improving the quality and reliability of the grounding. A relationship has been established between the ability to retain moisture and the magnitude of seasonal fluctuations in the electrical resistance of the soixl, and also the season factor, which takes into account changes under different climatic environmental conditions. The issues of application of various methods of reducing the resistivity of the soil during mounting of grounding devices are considered. One of the main ways to reduce ground resistance is the use of solutions of various mineral salts. This method is not optimal, as it accelerates the corrosion processes in the materials of the ground electrodes. Therefore, the paper also considers other ways to reduce the resistance of the ground loop; in particular, the authors propose a method for reducing the resistance of a grounding device based on the method of partial replacing the soil in the near-electrode region with a mixture with a lower resistivity capable of collecting moisture based on graphite and hydrogel. This type of mixture is environmentally friendly when used, as well as it is non-aggressive to the material of the ground loop. The principle of operation of this mixture is based on the fact that the hydrogel makes it possible to stabilize the moisture at the site of laying the circuit, while graphite increases the overall conductivity of the mixture. The paper presents the results of laboratory studies, which have been carried out in accordance with GOST 9.602–2016. For this purpose, control samples were placed in containers made of a non-conductive material (plexiglas) and dependence of resistivity on moisture, temperature, specific content of graphite and hydrogel was measured. The article presents graphs of the dependences of the mixture specific resistance on moisture, temperature, and the quantitative content of the hydrogel. From the results obtained, it can be concluded that the mixture in can be used in the energy sector to improve the reliability of electrical installations and ensure electrical safety.

About the Authors

I. A. Pavlovich
Belarusian State Agrarian Technical University
Belarus

Minsk



S. M. Baraishuk
Belarusian State Agrarian Technical University
Belarus

Address for correspondence:
Baraishuk Siarhei M. –
Belarusian State Agrarian Technical University,
99, Nezavisimosty Ave., 
223023, Minsk, Republic of Belarus/ 
Tel.: +375 29 775-76-37
bear_s@rambler.ru



References

1. Vedeneeva L. M., Chudinov A. V. (2017) Investigation of the Influence of the Basic Properties of Soil on the Resistance of Grounding Devices. Vestnik Permskogo Natsional'nogo Issledovatel'skogo Politekhnicheskogo Universiteta. Geologiya. Neftegazovoe i Gornoe Delo = Bulletin of PNRPU. Geology. Oil & Gas Engineering & Mining, 16 (1), 89–100 (in Russian).

2. IEEE Std 142–2007. IEEE Recommended Practice for Grounding of Industrial and Commercial Power Systems. Approved 7 June 2007. 225. https://doi.org/10.1109/ieeestd.2007.4396963.

3. Drako M. A. (2019) Corrosion of Grounding Conductors of Electrical Installations. Energeticheskaya Strategiya [Power Strategy], (6), 44–48 (in Russian).

4. Vedeneeva L. M., Chudinov A. V. (2016) Investigation of the Influence of Soil Moisture and Porosity on the Value of Their Conductivity. Vestnik PNIPU. Bezopasnost' i Upravlenie Riskami [Bulletin of the Perm National Research Polytechnic University. Safety and Risk Menagement], (5), 119–130 (in Russian).

5. Kucherenko D. E., Grishchenko D. N. (2018) The Influence of Soil Features on the Calculation and Design of the Storage Device. Colloquium-Journal, (12–6) (23), 84–90 (in Russian).

6. Baraishuk S. M., Pavlovich I. A., Kakhotsky M. I. (2020) Reduction of Seasonal Fluctuations in the Resistance to the Spreading of the Current of Grounding Devices Using Mixtures to Stabilize Soil Moisture. Epokha Nauki [The Age of Science], (24), 87–93 (in Russian).

7. Zhuang Chijie, Zeng Rong, Zhang Bo, HE Jin-Liang (2008) Grounding System Design Method in High Soil Resistivity Regions. Gaodianya Jishu/High Voltage Engineering, 34 (5), 893–897 (in Chinese).

8. Vilson L. C., Piantini A., Almaguer H. A. D., Coelho R. A., Boaventura W. C., Paulino J. O. S. (2015) The Influence of Seasonal soil Moisture on the Behavior of Soil Resistivity and Power Distribution Grounding Systems. Electric Power Systems Research, 118, 76–82. https://doi.org/10.1016/j.epsr.2014.07.027.

9. Drako M.A., Baraishuk S. M., Pavlovich I. A. (2021) Compound Mixtures Based on Hydrolyzed Polyacrylonitrilereducing Soil Electrical Resisctivity. Power Engineering: Research, Equipment, Technology, 23 (1), 80–92. https://doi.org/10.30724/1998-9903-2021-23-1-80-92 (in Russian).

10. Tung C. C., Lim S. C. (2017) Performance of electrical Grounding System in Soil at Low Moisture Content Condition at Various Compression Levels. Journal of Engineering Science and Technology, 12 (Special Issue), 27–47.

11. Gribanov A. N. (2016) Bipron: Grounding of Electrical Installations. Ekspozitsiya Neft' Gaz = Exposition Oil & Gas, (4), 72–75 (in Russian).

12. Kirkpatrick E. L. The Conflict Between Copper Grounding Systems and Cathodic Protection Systems. Avaialable at: https://www.elkeng.com/pdfs/6-The-Conflict-Between-Copper-GroundingCP122001.pdf.

13. Barayihuk S. M., Pavlovich I. A., Murodov M. H., Abdullaev H., Skripko A. N. (2021) Reducing the Resistance of Grounding Devices by Using Soil Treatment with Moisture-Stabilizing Additives that Are Not Aggressive to the Grounding Material. Agropanоrama, (5), 28–33 (in Russian).

14. Pavlovich I. A., Barayshuk S. M., Murodov M. H. (2021) Temperature Dependence of the Resistivity of Soil-Substituting Composite Mixtures for the Optimization of Grounding. Energosberezhenie – Vazhneishee Uslovie Innovatsionnogo Razvitiya APK: Materialy Mezhdunarodnoi Nauchno-Tekhnicheskoi Konferentsii, Minsk, 21–22 Dekabrya 2021 g. [Energy Saving as the Most Important Condition for the Innovative Development of the Agro-Industrial Complex: Proceedings of the International Scientific and Technical Conference, Minsk, December 21–22, 2021] Minsk, BGATU, 230–232 (in Russian).

15. Professional Knowledge Center Zandz. Com on Lightning Protection and Grounding. Available at: https://zandz.com/ru/ (accessed 24 October 2022) (in Russian).

16. TKP 339-2011(02230) Electrical Installations for Voltage up to 750 kV. Power Transmission Lines, Overhead and Current Lines, Distribution and Transformer Substations, Electric Power and Battery Installations, Electrical Installations of Residential and Public Buildings. Rules and Protective Measures of Electrical safety. Electricity Accounting. Norms of Acceptance Tests. Minsk, Ministry of Energy of the Republic of Belarus, 2011. 593 (in Russian).

17. SN 4.04.03-2020 Lightning Protection of Buildings, Structures and Utilities. Minsk, Ministry of Architecture and Construction of the Republic of Belarus, 2020. 161 (in Russian).


Review

For citations:


Pavlovich I.A., Baraishuk S.M. Reduction of the Electrical Resistance of Grounding Devices by the Use of a Soil Replacement Mixture Based on Graphite and Hydrogel to Stabilize the Electrophysical Parameters of the Soil. ENERGETIKA. Proceedings of CIS higher education institutions and power engineering associations. 2023;66(4):322-332. (In Russ.) https://doi.org/10.21122/1029-7448-2023-66-4-322-332