Preview

Methods of Current Limitation in Low Voltage (up to 1 kV) Electric Networks

https://doi.org/10.21122/1029-7448-2021-64-6-492-504

Abstract

The article discusses and systematizes the causes of high values of short-circuit currents in electrical networks up to 1 kV and indicates their negative consequences. A brief analysis of some current limiting methods (both with and without additional investment) is given, which makes it possible to reduce the negative effects when significant short-circuit currents occur. The variants of the implementation of these current limiting methods recommended for study at the design stage or when replacing equipment that has exhausted its resource, are considered. The advantages and disadvantages of the methods of limiting short-circuit currents described in the article are indicated. Options for connecting equipment with low power consumption to nodes of the electrical network up to 1 kV with high values of short-circuit currents are also considered. Special attention is paid to current-limiting protection devices, a detailed description of the design of some of them is given, the advantages of their use in comparison with other current-limiting methods are indicated, the corresponding graphs of the limitation of the periodic component of the short-circuit current, shock short-circuit current and thermal pulse are presented. Based on the analysis of graphic materials, the issue of ensuring the selectivity of protections is considered. The degree of prevalence of equipment with the property of current limitation is determined. A method for determining selective current-limiting protection devices is given, viz. the method of energy selectivity, the corresponding graphs for determining energy selectivity are presented. The physics allowing to determine the degree of efficiency of limiting the short-circuit current is described. Recommendations on the use of current-limiting equipment are proposed.

About the Authors

A. Yu. Kapustsinski
Belarusian National Technical University; “ENECA” ALC
Belarus

Minsk



S. V. Kanstantsinava
Belarusian National Technical University
Belarus

Address for correspondence: Kanstantsinava Sviatlana V. Belаrusian National Technical University, 65/2, Nezavisimosty Ave., 220013, Minsk, Republic of Belarus Теl.: +375 17 292-65-52 
svkon2000@gmail.com



References

1. Rules for the Arrangement of Electrical Installations. The Sixth Edition, Revised and Supple-mented, with Changes. Moscow, Energoatomizdat Publ., 1986. 648 (in Russian).

2. Schneider Electric (2006) Schneider Electric Technical Collection. Iss. 4. Coordination of Low Voltage Protections. Available at: https://www.electrocentr.com.ua/files/documentation/SE/TechLibrary/Vipusk4-Koordinacia_zashit.pdf (in Russian).

3. State Standard IEC 60947-2–2014. Low-Voltage Distribution and Control Equipment. Part 2. Circuit Breakers. Minsk, Interstate Council for Standardization, Metrology and Certification, 2014. 128 pp. (in Russian).

4. State Standard IEC 60269-1-2016. Low-Voltage Fuses. P. 1. General requirements. Minsk, In-terstate Council for Standardization, Metrology and Certification, 2016. 68 pp. (in Russian).

5. The Principle of Operation of the Fuse. Kursk Electrical Equipment Plant. 2016. Available at: https://keaz.ru/company/press-center/blog/2016/864-princip-raboti-i-ustroystvo-predohranitelya (accessed 20 May 2021) (in Russian).

6. State Standard IEC 60898-1-2020. Small-Sized Electrical Equipment. Circuit Breakers for Pro-tection Against Overcurrents for Household and Similar Purposes. Part 1. Circuit Breakers for Alternating Current. Minsk: Interstate Council for Standardization, Metrology and Certification, 2020. 124 pp. (in Russian)

7. EKF (2020) Electrical Products for Professionals: Master Catalog No. 29, 2020. Available at: https://ekfgroup.com/uploads/pos-articles/2020-05/master-katalog-29.pdf (in Russian).

8. Schneider Electric (2019) Acti 9. Efficiency Worthy of You. Available at: https://shop.idelectro.ru/upload/docs/%D0%9A%D0%B0%D1%82%D0%B0%D0%BB%D0%BE%D0%B3%20Acti9%202019.pdf (in Russian).

9. State Standard 26522-85. Short Circuits in Electrical Installations. Minsk: Interstate Council for Standardization, Metrology and Certification, 1985. 20 pp. (in Russian)

10. Low-Voltage Equipment. Protection on Fuses. Load Switches with Fuses [Electronic Re-source]. Available at: https://library.e.abb.com/public/3b93e50521914de6b2d24fd13c6892af/Fusegear.pdf. (accessed 03 June 2021) (in Russian).

11. Kapustsinski A. Yu., Kаnstantsinava S. V. (2021) Increasing the Sensitivity of Protections in Electrical Networks up to 1 kV by Using Microprocessor and Semiconductor Release Tripping Devices. Enеrgеtika. Izvestiya Vysshikh Uchebnykh Zavedenii i Energeticheskikh Ob’edinenii SNG = Energetika. Proceedings of CIS Higher Education Institutions and Power Engineering Associations, 64 (5). 393–407 (in Russian). https://doi.org/10.21122/1029-7448-2021-64-5-393-407

12. Low-Voltage Equipment. Load Switches up to 4000 A. Technical Catalog. Available at: https://www.abn.ru/files/abb/Catalogue_Switches.pdf. (accessed 03 June 2021) (in Russian).

13. Konstantinova S. V., A. Kapustinskii Yu., Yaroshevich T. M. (2021) Calculation of the Capacity for the Operation of a Mini-Energy Complex Based on an Independently Operating Asynchro-nous Generator. Enеrgеtika. Izvestiya Vysshikh Uchebnykh Zavedenii i Energeticheskikh Ob’edinenii SNG = Energetika. Proceedings of CIS Higher Education Institutions and Power Engineering Associations, 64 (1), 40–50 (in Russian). https://doi.org/10.21122/1029-7448-2021-64-1-40-50


Review

For citations:


Kapustsinski A.Yu., Kanstantsinava S.V. Methods of Current Limitation in Low Voltage (up to 1 kV) Electric Networks. ENERGETIKA. Proceedings of CIS higher education institutions and power engineering associations. 2021;64(6):492-504. (In Russ.) https://doi.org/10.21122/1029-7448-2021-64-6-492-504

Views: 701


Creative Commons License
This work is licensed under a Creative Commons Attribution 4.0 License.


ISSN 1029-7448 (Print)